VCP 6-45 dust fans

VCP 6-45 dust fans
Fan radial dust one-sided suction for moving air and other gas mixtures with temperatures up to + 80°С. In the moving air flow, the concentration of solid mechanical dust impurities does not exceed 300 g/m3, there are no sticky and fibrous contaminants. It is used in systems of dust-cleaning installations and pneumatic transport, for removal of wood, metal dust and shavings. It is made of carbon and stainless steel, aluminum alloys and dissimilar metals.

Leave a request

Leave your phone number and email. Our manager will confirm the configuration, price and lead time.

Or contact us directly (044) 238-86-63 (067) 113-88-18 vent@ventzavod.com Mon–Fri, 8:00–20:00
Execu­tion D/Dn N en, KW n en,
rpm
n w.w. en,
rpm
Airflow
m3/h
Pressure
Pa
ID
ηmax in working zone ηmax in working zone

ВЦП 6-45 №5

5.1 1 2.2 1500 1345 3390 1400-6050 784 846-496 id37713
5.1 1 3 1500 1489 3750 1550-6710 963 1039-610 id37714
5.1 1 4 1500 1602 4040 1660-7220 1115 1204-706 id9877
5.1 1 5.5 1500 1812 4560 1880-8160 1423 1535-902 id9887
5.1 1 7.5 1500 2030 5110 2110-9050 1786 1928-1142 id9890
5.1 1 11 3000 2278 5740 2370-10260 2256 2434-1428 id37715
5.1 1 15 3000 2486 6250 2580-11700 2676 2888-1694 id37716
5.1 1 18.5 3000 2630 6620 2730-11840 3000 3226-1901 id37717

ВЦП 6-45 №6,3

5.1 1 4 1000 1108 5600 2310-9940 844 913-536 id37718
5.1 1 5.5 1500 1230 6210 2560-11020 1038 1124-658 id37719
5.1 1 7.5 1500 1373 6940 2860-12320 1297 1404-822 id37720
5.1 1 11 1500 1531 7740 3190-13730 1611 1745-1021 id9895
5.1 1 15 1500 1740 8800 3630-15600 2082 2256-1318 id9898
5.1 1 18.5 1500 1845 9320 3850-16540 2338 2532-1481 id9900
5.1 1 22 1500 1927 9750 4020-17310 2555 2764-1621 id9901
5.1 1 30 1500 2090 10580 4360-18780 3009 3257-1907 id9904

ВЦП 6-45 №8

5.1 1 30 1500 1285 13330 6810-24490 1929 2160-1253 id9913
5.1 1 37 1500 1440 14930 7600-27970 2369 2705-1601 id9914
5.1 1 45 1500 1600 16600 8480-30230 2991 3345-1978 id9915
VCP 6-45 dust fans

Fans are manufactured in accordance withTU U 28.2-24881057-003:2023:

  • from carbon steel;
  • from stainless steel;
  • from dissimilar metals;
  • from aluminum alloys.

VCP 6-45 centrifugal dust fans is one of the most popular types of ventilation equipment in its class.

Fans are intended for use in rooms where the concentration of solid mechanical dust impurities in the moving air stream does not exceed 300 g/m3. The air temperature should not exceed +80 °С. There should not be any contamination that has a fibrous structure or sticky properties.

VCP 6-45 fans are used:

  • in dust-cleaning systems installations;
  • in pneumatic transport systems;
  • for the removal of wood dust and shavings;
  • for remove metal dust and shaving.

General information about fans:

  • Single suction;
  • Spiral rotary body;
  • Radial blades;
  • Quantity of blades 8;
  • Direction of rotation – right and left.
Инфоблок

Depending on the direction of rotation, the fans are produced in the right or left rotation. Right-hand fans with a wheel rotating clockwise, left rotation – with a wheel rotating counter-clockwise when viewed from the suction side of the fan.